GIDM
INDUSTRIAL / COMMERCIAL
PACKAGED FURNACES
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
(Suitable for Operation with up to 100% Fresh Air)
READ MANUAL CAREFULY BEFORE INSTALLING
OR OPERATING THE FURNACE
FOR YOUR SAFETY FOR YOUR SAFETY
If you smell gas follow these
instructions,
The use and storage of gasoline or other
flammable vapors and liquids in open
1) Open windows. containers in the vicinity of this appliance
2) Do not touch electrical switches. is hazardous.
3) Extinguish any open flame.
4) Call the gas supplier immediately.
MODEL: SERIAL NUMBER:
JOB: DATE OF INSTALLATION:
WARNING
IMPROPER INSTALLATION, ADJUSTMENT, SERVICE OR MAINTENANCE CAN
CAUSE PROPERTY DAMAGE, INJURY OR DEATH. PLEASE READ THE
INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTION
THOROUGHLY.
*THIS UNIT IS TO BE SERVICED BY QUALIFIED PERSONNEL*
**DO NOT TAMPER WITH THE UNIT OR CONTROLS**
INSTALLER’S RESPONSIBILITY
Installer please note: This equipment has been test fired and inspected. It has been shipped free from defects from
our factory. However, during shipment and installation, problems such as loose wires, leaks or loose fasteners may
occur. It is the installer’s responsibility to inspect and correct any problems that may be found.
INSTALLER/SERVICE CONTRACTOR
NAME:
ADDRESS:
TELEPHONE:
CONTACT:
Vedere la pagina 0
1 2 3 4 5 6 ... 28 29

Sommario

Pagina 1

GIDM INDUSTRIAL / COMMERCIALPACKAGED FURNACES I

Pagina 2

9NOTE: Refer to manufacturer literature provided for maintenance requirements of optional equipment.BEARING INSTALLATION AND MAINTENANCENOTE: To pre

Pagina 3

10Table 1. Recommended LubricationBall Bearings Roller BearingsShaft Size(inches)Grease Charge(ounces)Shaft Size(inches)Grease Charge(ounces)1/4 t

Pagina 4

11 TENSIONING V-BELT DRIVES 1. Ideal tension is the lowest tension at which the belt will not slip under peak load conditions. 2. Check tension

Pagina 5

12GIDM INDUSTRIAL HEATER - WARRANTYI.C.E. MFG. LTD. WARRANTS THAT IT WILL SUPPLY TO OR REPAIR FOR THE PURCHASER OF THISPACKAGE UNIT HEATER THE HEAT EX

Pagina 6

13ECONOMITE 400-33 & F400-33 GAS BURNERSINITIAL START UP AND ADJUSTMENTCAUTION: Only qualified service personnel should attempt initial start-up.

Pagina 7

1422. Make the final setting of the air shutter by checking the flue gases with an “Orsat” or other similar combustiontesting instrument. There shou

Pagina 8

15ECONOMITE 400-33 & F400-33 GAS BURNERS WARNING: Explosion hazard. Can cause serious injury or death. This device can malfunction if it g

Pagina 9

16GP TYPE C FORCED DRAFT BURNER C-6.2 TO C-12.9INITIAL START UP1. Make sure burner power switch is off and manual main and pilot valves are closed.2.

Pagina 10

17BURNER SAFETY CHECK1. Start and stop burner several times to ensure proper operation.2. Check operation of combustion safeguard control by simulat

Pagina 11

BLOWER/FILTERSECTIONSHIPPED IN SECTIONS TO JOB SITE.SECTIONS BY CONTRACTORS ON UNITS SOME FIELD WIRING TO BE CONNECTED BETWEEENNOTE:HEATING SECTION C

Pagina 12 - PER INCH OF SPAN

1RECEIVING AND WAREHOUSINGInspect the unit upon arrival for any shipping damage. If any part is missing or damaged, notify the carrier at once.If the

Pagina 13

DCBA36" MIN. ABOVEHIGHEST POINTON BUILDINGERAIN CAPEXHAUST STACK14 GA. NON-CORROSIVESTEELWEATHER SKIRTROOFROOFFRAMINGSTACKSUPPORTMETALSLEEVEINDIR

Pagina 14

BURNER MOTORLOW & HIGH BUTTERFLY SETTINGSHORT CRANK ARMGIDM GRAVITY VENTED F-400-33 BURNER( DECREASE THE DISTANCE BETWEEN DRIVE ROD AND CENTER PIN

Pagina 15

LINKAGE OPERATION (GRAVITY VENT)BURNER DAMPERBUTTERFLYDAMPERARMLOW FIRESET SCREWHIGH FIRESET SCREWBUTTERFLY DAMPER PINHIGH FIRETRAVELPOP UP DOORPRESSU

Pagina 16

IGNITION ELECTRODE:THE IGNITION ELECTRODE IS POSITIONED AS SHOWN, WITH THE HORIZONTAL PART OF THE ELECTRODE FLUSH WITH THE DIFFUSER PLATE, LEAVING A G

Pagina 17

1 23 4567891012131415161243786513141615111210911SIGHT GLASS & SEALREAR COVER PLATDAMPER CONTROLFAN BOXPILOT REGULATOR & SOLENOIDPILOT SHUT

Pagina 18

BOTTOM DISCHARGEROOF CURB DETAILONE EXAMPLE OF CURBINGINSULATION (BY OTHERS)NEOPRENE GASKETOR CAULKING (BY OTHERS)CANT STRIP (BY OTHERS)ROOFING PAPER(

Pagina 23 - 1/16" - 1/8"

2For service, it is advisable to maintain a minimum 24-inch clearance on the side opposite the controls and 42-inchclearance on the control side. If

Pagina 24 - 1:1 FIG VII

31) FOR POWER VENTED UNITS: The flue draft should be adjusted at the damper of the induceddraft fan when the unit is operating on high fire. The ov

Pagina 25

4*A tee shall be installed in the supply line at the same elevation as the gas inlet connection. The tee must beequipped with a nipple and pipe cap t

Pagina 26

55. Lubricate (if necessary) the burner, induced draft fan and main fan motors. The specifications on the motors for grease and oil shall

Pagina 27

65. Check supply fan motor load against rating plate figure. If actual figure is significantly different than the ratingplate value, take corrective

Pagina 28

7The equipment has been electrically and fire tested prior to shipment. However, during transit, misadjustment ofcontrols and loose wires could devel

Pagina 29

86. UNABLE TO ADJUST FIRE TO BURN CLEANLY.A) Insufficient exhauster* draft.B) Insufficient or too much fuel at supply.C) Incorrect adjustment o